Unit installation

July 2008 Application Note 1004
©2012 Mitsubishi Electric US, Inc.
P a g e | 3
Note: All wiring shall comply with NEC and local electrical codes.
Refer to unit installation manual for more details.
CONNECTING WIRES AND CONNECTING GROUND WIRE
Use a solid conductor or stranded conductor AWG14.
Use doubled insulated copper wire with 300 volt
insulation.
Use copper conductors only.
Follow national and local electrical code.
POWER SUPPLY CABLE AND GROUND WIRE
Use solid or stranded conductor AWG12** or AWG14
wire.
Use copper conductors only.
Follow national and local electrical code.
Due to continuing improvement, above specification may be subject to change without notice.
2013 P-Series and M-Series - Application Notes (June 2013)