Service manual

42
MUZ-A24NA MUY-A24NA MUZ-GA24NA MUY-GA24NA
The left lamp of
OPERATION INDICATOR
lamp (Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C. board)
Condition Correspondence
Indoor/outdoor
unit failure
mode recall
function
LED1 LED2
OFF None (Normal)
Lighting Lighting
2-time ash
Outdoor power system Lighting Lighting IPM protection stop or lock protection stop is
continuously performed 3 times within 1 minute
after the compressor gets started, or converter
protection stop or bus-bar voltage protection
stop is continuously performed 3 times within 3
minutes after start-up.
• Check the connection of the
compressor connecting wire.
• Refer to 10-5. "How to
check inverter/compressor".
• Check the stop valve.
3-time ash
Discharge temperature
thermistor
Lighting Once Thermistor shorts or opens during compressor
running.
• Refer to 10-5. "Check of
outdoor thermistors".
Defrost thermistor (MUZ) Lighting Once
Ambient temperature
thermistor
Lighting Twice
Fin temperature thermistor Lighting 3 times
P.C. board temperature
thermistor
Lighting 4 times • Replace the outdoor
electronic control P.C. board.
Outdoor heat exchanger
temperature thermistor
Lighting 9 times • Refer to 10-5.
"Check of
outdoor thermistors".
4-time ash
Overcurrent Once Goes out 28 A current ows into intelligent power module. • Reconnect compressor
connector.
• Refer to 10-5. "How to
check inverter/compressor.
• Check the stop valve.
5-time ash
Discharge temperature Lighting Lighting Discharge temperature exceeds 241°F (116°
C) during operation. Compressor can restart if
discharge temperature thermistor reads 212°F
(100°C) or less 3 minutes later.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 10-5. "Check of
LEV".
6-time ash
High pressure Lighting Lighting The outdoor heat exchanger temperature
exceeds 158°F (70°C) during cooling or the
indoor gas pipe temperature exceeds 158°F (70
°C) during heating.
• Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
7-time ash
Fin temperature 3 times Goes out The n temperature exceeds 189°F (87°C)
during operation.
• Check around outdoor unit.
• Check outdoor unit air
passage.
• Refer to 10-5. "Check of
outdoor fan motor".
P.C. board temperature 4 times Goes out The P.C. board temperature exceeds 158°F (70°
C) during operation.
8-time ash
Outdoor fan motor Lighting Lighting Failure occurs continuously three times within
30 seconds after the fan gets started.
• Refer to 10-5. "Check of
outdoor fan motor".
9-time ash
Nonvolatile memory data Lighting 5 times Nonvolatile memory data cannot be read
properly.
• Replace the outdoor
electronic control P.C. board.
10-time ash
Discharge temperature Lighting Lighting The frequency of the compressor is kept 80 Hz
or more and the discharge temperature is kept
under 102°F (39°C) for more than 20 minutes.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 10-5. "Check of
LEV".
11-time ash Communication error between
P.C. boards
Lighting 6 times Communication error occurs between the
electronic control P.C. board and power board
for more than 10 seconds.
Check the connecting wire
between outdoor electronic
control P.C. board and
power board.
The communication between boards protection
stop is continuously performed twice.
Current sensor Lighting 7 times A short or open circuit is detected in the current
sensor during compressor operating.
Replace the power board.
Current sensor protection stop is continuously
performed twice.
Zero cross detecting circuit 5 times Goes out Zero cross signal cannot be detected while the
compressor is operating.
Check the connecting wire
among electronic control
P.C. board, noise lter P.C.
board and power board.
The protection stop of the zero cross detecting
circuit is continuously performed 10 times.
Converter 5 times Goes out A failure is detected in the operation of the
converter during operation.
• Check the voltage of power
supply.
Replace the power board.
Bus-bar voltage
(1)
5 times Goes out The bus-bar voltage exceeds 400 V or falls to
200 V or below during compressor operating.
Bus-bar voltage
(2)
Even if this protection stop
is performed continuously
3 times, it does not mean
the abnormality in outdoor
power system.
6 times Goes out The bus-bar voltage exceeds 400 V or falls to 50
V or below during compressor operating.
• Check the voltage of power
supply.
• Replace the outdoor
electronic control P.C. board.
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.).