Service manual

37
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds 15 seconds
MUZ-A09NA MUZ-A12NA MUZ-A15NA MUZ-A17NA MUZ-A24NA
MUY-A15NA MUY-A17NA MUY-A24NA MUZ-GA24NA MUY-GA24NA
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
8-2. R.V. COIL CONTROL(MUZ)
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling
. . . . . . . . . . . . . . . . .
OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
<MUZ-A09/12/15/17>
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
ON or OFF
ON or OFF
R.V.coil
<MUZ-A24,MUZ-GA24>
ON
OFF
ON or OFF
ON or OFF
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
<MUZ-A09/12/15/17, MUY-A15/17>
Sensor Purpose
Actuator
Compressor LEV
Outdoor fan
motor
R.V. coil
Indoor fan
motor
Discharge temperature thermistor
Protection
○○
Indoor coil temperature thermistor
Cooling: Coil frost prevention
Heating: High pressure protection
○○
Defrost thermistor
Cooling: High pressure protection
○○
Heating: Defrosting
○○○○○
Fin temperature thermistor Protection
○○
Ambient temperature thermistor
Cooling: Low ambient temperature operation
○○○
<MUZ-A24, MUY-A24, MUZ-GA24, MUY-GA24>
Sensor Purpose
Actuator
Compressor LEV
Outdoor fan
motor
R.V. coil
Indoor fan
motor
Discharge temperature thermistor
Protection
○○
Indoor coil temperature thermistor
Cooling: Coil frost prevention
Heating: High pressure protection
○○
Defrost thermistor (MUZ) Defrosting
○○○○○
Fin temperature thermistor Protection
○○
Outdoor heat exchanger temperature
High pressure protection
○○○
Ambient temperature thermistor
Cooling: Low ambient temperature
operation
○○○
8
ACTUATOR CONTROL