8-6. TROUBLESHOOTING FLOW
 A Check of indoor fan motor
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
Turn OFF the power supply.
Is there any foreign matter that interferes 
the rotation of the line fl ow fan?
Yes
No
Remove the foreign matter and 
adjust the line fl ow fan.
Pay careful attention to the high voltage on the fan motor connector CN211.
Turn ON the power supply, wait 5 seconds or more, and then press 
EMERGENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds after EMER-
GENCY OPERATION switch is pressed.
If more than 12 seconds passes by, turn OFF the power supply and 
turn ON it again, then measure the voltage. 
1. Measure the voltage between CN211  (+) and 
(-).
2. Measure the voltage between CN211 
(+) and  (-).
 If more than 12 seconds passes after EMERGENCY OPERATION switch 
is pressed, the voltage mentioned above 2 goes 0 VDC although the 
indoor electronic control P.C. board is normal
Is there 162 VDC between CN211 
(+) and  (-), and does the voltage 
between CN211 
(+) and  (-) rise 
to the range of 3 to 6 VDC within 12 
seconds after EMERGENCY OPERA-
TION switch is pressed?
Replace the indoor fan motor.
CN211
Indoor electronic 
control P.C. board
Yes
No
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211 
(+) and  (-) while the fan motor is 
rotating.
Replace the indoor electronic control P.C. board.
Is it unchanged holding 
0 or 15 VDC?
No
(Changed)
Yes
(Unchanged)
Replace the indoor electronic control P.C. board.
Replace the indoor fan motor.