Quick start manual

Notes on the net work settings:
(a) In the exam ple only one servo ampli fier is con nected to the CC-Link net work. This value must
be increased by the num ber of slave sta tions installed if appli ca ble.
(b)These val ues spec ify which bits or data words are to be used to con trol the servo ampli fier.
The set tings shown in the exam ple are for the fol low ing assign ments:
(c) Slave sta tion type set ting:
d
Con nect the PC to the PLC and trans fer the mod i fied pro ject to the con trol ler.
NOTE If the CC-Link con nec tion to the servo am pli fier is es tab lished suc cess fully the L.RUN, SD
und RD sta tus LEDs on the servo am pli fier will light up.
Positioning via a CC-Link Network CC-Link Communication Settings
MR-J3-T 5 - 37
Fig. 5-7: This con fig u ra tion also en ables ex change of data words
PLC -> Servo Amplifier Servo Am pli fier -> PLC
PLC I/Os Re gis ters Sig nals PLC I/Os Re gis ters Sig nals
Y100 RYn0 SON X100 RXn0 RD
Y101 RY n 1 ST1 X101 RXn1 INP
Y102 RYn 2 ST2 X103 RXn3 ZP
Y103 RYn3 DOG X11A RX(n+1)A ALM
Y104 RYn4 LSP
Y105 RYn5 LSN
NOTE:
Sig nals DI5, DI6 and DI7 are only avail able
when the am pli fier is con fig ured to oc cu py 2
sta tions in the net work.
Y106 RYn6 MD0
Y10A RYnA DI0
Y10B RYnB DI1
Y10C RYnC DI2
Y10D RYnD DI3
Y10E RYnE DI4
Y10F RYnF RES
Table 5-1: Sig nal assignments