Quick start manual

4.5 Functional Test of Digital Input Positioning
Nor mally you need a sim ple con trol ler to set the dig i tal inputs used to select the point table posi -
tion entries, for exam ple a PC, a mini PLC or an HMI con trol ter mi nal. This chap ter explains how
you can per form a thor ough check of the func tion al ity of the posi tion ing con trol func tions with out
need ing to per form the addi tional work of pro gram ming and install ing a con trol ler.
Fig. 4-19 shows a test instal la tion with out an exter nal con trol ler. Note that the FX Sim u la tion Box
used in this setup can set a max i mum of 14 dig i tal inputs.
NOTE The test setup shown above does not use any safety fea tures for the tests (EMG. OFF). You
should thus only use this setup in a con trolled test en vi ron ment where er rors can not cause
any dan ger for per son nel or equip ment!
Functional Test of Digital Input Positioning Positioning with Digital Inputs
4 - 28 MITSUBISHI ELECTRIC
Fig. 4-19: Test setup for sim u lat ing po si tion ing with dig i tal inputs
1-pha se
200–230V AC
Servo motor
PC
FX Simulation Box
24V DC
24V DC
power supply
Motor
Encoder
Encoder cable
1 MR-J3USBCBL3M
Cable length: 3m
2 MR-J2CMP2
3 MR-J2M-CNT1TBL-M
Cable length: 0.5–1m
4 MR-TB50