Instruction manual
3 - 23
3. SIGNALS AND WIRING
Control
mode
Device Symbol
Connec-
tor pin
No.
Functions/Applications
I/O
division
PST
Proportion control PC CN1-17 Turn PC on to switch the speed amplifier from the proportional
integral type to the proportional type.
If the servo motor at a stop is rotated even one pulse due to any
external factor, it generates torque to compensate for a position shift.
When the servo motor shaft is to be locked mechanically after
positioning completion (stop), switching on the proportion control
(PC) upon positioning completion will suppress the unnecessary
torque generated to compensate for a position shift.
When the shaft is to be locked for a long time, switch on the
proportion control (PC) and torque control (TL) at the same time to
make the torque less than the rated by the analog torque limit.
DI-1
Emergency stop EMG CN1-42 Turn EMG off (open between commons) to bring the motor to an
emergency stop state, in which the base circuit is shut off and the
dynamic brake is operated.
Turn EMG on (short between commons) in the emergency stop state
to reset that state.
DI-1
Clear CR CN1-41 Turn CR on to clear the position control counter droop pulses on its
leading edge. The pulse width should be 10ms or more.
The delay amount set in parameter No. PB03 (position command
acceleration/deceleration time constant) is also cleared.
When the parameter No. 42 setting is "
1 ", the pulses are
always cleared while CR is on.
DI-1
Electronic gear
selection 1
CM1 When using CM1 and CM2, make them usable by the setting of
parameters No. PD03 to PD08, PD10 to PD12.
The combination of CM1 and CM2 gives you a choice of four
different electronic gear numerators set in the parameters.
CM1 and CM2 cannot be used in the absolute position detection
system.
DI-1
(Note) Input signals
CM2 CM1
Electronic gear molecule
0 0 Parameter No. PA06
0 1 Parameter No. PC32
1 0 Parameter No. PC33
1 1 Parameter No. PC34
Electronic gear
selection 2
CM2
Note. 0: off
1: on
DI-1
Gain changing CDP When using this signal, make it usable by the setting of parameter
No. PD03 to PD08, PD10 to PD12.
Turn CDP on to change the load inertia moment ratio and gain
values into the parameter No. PB29 to PB32 values.
DI-1