Instruction manual

4 - 3
4. STARTUP
2) When regenerative brake option is used over 5kW
The lead of built-in regenerative brake resistor connected to P terminal and D terminal of TE1
terminal block should not be connected.
The generative brake option should be connected to P terminal and C terminal.
A twisted cable should be used when wiring is over 5m and under 10m. (Refer to Section 12.2)
3) When brake unit and power supply return converter are used over 5kW
The lead of built-in regenerative brake resistor connected to P terminal and D terminal of TE1
terminal block should not be connected.
Brake unit or power supply return converter should be connected to P terminal and N terminal. (Refer
to Section 12.3 and 12.4)
4) The power factor improving DC reactor should be connected across P
1
-P
2
. (Refer to Section 12.10.)
P
1
P
2
Servo amplifier
(Note)
Power factor
improving DC
reactor
Note. Always disconnect the wiring across P
1
-P
2
.
(2) I/O signal wiring
(a) The I/O signals should be connected correctly.
Use DO forced output to forcibly turn on/off the pins of the CN1 connector. This function can be used to
perform a wiring check. (Refer to Section 6.8.) In this case, switch on the control circuit power supply
only.
(b) 24VDC or higher voltage is not applied to the pins of connectors CN1.
(c) SD and DOCOM of connector CN1 is not shorted.
DOCOM
SD
CN1
Servo amplifier
4.1.3 Surrounding environment
(1) Cable routing
(a) The wiring cables are free from excessive force.
(b) The encoder cable should not be used in excess of its flex life. (Refer to Section 11.4.)
(c) The connector part of the servo motor should not be strained.
(2) Environment
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.