Specifications
3-4
(4) CC-Link terminal block (CN10) wiring method
(a) Strip the cable and separate the internal wires and braided shield.
(b) Strip the braided shield and internal wires, and twist the conductors.
3-core twisted pair cable
Approx. 10mm (0.394in.
)
Braided shield
(c) Twist the same wires or braided shields of the cable connected to the preceding axis
or PLC and the cable connected to the next axis into one piece.
(d) For the last axis, work on the terminating resistor, which is supplied with the CC-
Link unit, as shown below.
Terminating resistor
Cut
Remove insulation
(10mm (0.394in.))
Bend lead wire
(10mm (0.394in.))
Cut
Remove insulation
(e) Insert the conductors of the cables into the opening, and tighten them with a flat-
blade screwdriver so that the cables do not come off. (Tightening torque: 0.5 to
0.6N
m When inserting the cables into the opening, make sure that the terminal
screw is fully loose.
Loosen
Tighten
Opening
CC-Link terminal block
Cables
Flat-blade screwdriver
Tip thickness: 0.4 to 0.6mm (0.016 to 0.024in.)
Full width: 2.5 to 3.5mm (0.098 to 0.138in.)
To preceding station
or PLC
To next
station