Specifications
3-1
3. CC-Link COMMUNICATION FUNCTION
3.1 Communication Specifications
The MR-J2S-CP-S084
MR-J2S-T01 is equivalent to a remote device station.
For details of the PLC side specifications, refer to the CC-Link System Master Unit Manual.
Communication specification list
Unit Model MR-J2S-T01
Power supply
5VDC Supplied from servo amplifier.
Applicable CC-Link version
Ver.1.10
Applicable servo amplifier
MR-J2S-
CP -S084
Communication speed
10M / 5M / 2.5M / 625K / 156Kbps
Communication system
Broadcast polling system
Synchronization system
Frame synchronization system
Encoding system
NRZI
Transmission path format
Bus format (EIA RS485 compliant)
Error control system
CRC(X
16
X
12
X
5
1)
Connection cable Shielded three-core twisted pair cable
Transmission format HDLC compliant
Remote station number 1 to 64
Communication speed
156Kbps 625Kbps 2.5Mbps 5Mbps 10Mbps
Maximum overall cable
length
1200m 900m 400m 160m 100m
(Note)
Cable length
Interstation cable
length
0.2m or more
CC-Link
Number of connected units
Up to 42 units (when 1 station is occupied by one unit), (up to 32 units
when two stations are occupied by one unit) when there are only
remote device stations. Can be used with other devices.
Note: Change depending on the used cables. For details, refer to the CC-Link System Master/Local Unit
User's Manual.