Specifications

10-8
Class No.
Abbrev-
iation
Name and Function
Initial
Value
Unit
Setting
Range
Basic parameters
18 *DMD Status display selection
Select the status display shown at power-on.
0000 Refer to
name and
function
column.
Note: After setting the values of the parameters marked *, switch power off once. Switching power on again
completes the setting.
Selection of amplifier status display at
power-on
00: Current position
01: Command position
02: Command remaining distance
03: Point table No.
04: Cumulative feedback pulses
05: Motor speed
06: Droop pulses
07: For manufacturer setting
08: Torque limit voltage
09: Regenerative load ratio
0A: Effective load ratio
0B: Peak load ratio
0C: Instantaneous torque
0D: Within one-revolution position low
0E: Within one-revolution position high
0F: ABS counter
10: Load inertia moment ratio
11: Bus voltage
12: Option unit communication state