Specifications
48
BCN-B11127-478*
6.3 Detailed description of the signals
Index advanced and retard operation
The synchronous operation will start when synchronous operation signal (STS) become enabel.
The index advance and retard operation will start when advance or retard operation signal (ST1/ST2)
are turn on.
Note: 1.The speed of advance or retard operation can not change within the indexing. It will change next
operation.
2. ST1 / ST2 signals are effective after synchronous operation compliting.
Less than 10ms
More than
5ms
More than
5ms
In-position ON
(INP) OFF
Synchronous ON
completion (SYC) OFF
Overlapping ON
completion (SYF) OFF
Synchronous speed
(Synchronous pulse input)
Motor speed
Synchronous ON
operation OFF
(STS)
Advance Start ON
(ST1) OFF
Retard Start ON
(ST2) OFF