Specifications

24
BCN-B11127-478*
Code No. Item/Function
Reading data (RW
R3
) contents
(Servo amplifier
PLC)
0030
to
0035
Alarm occurrence time in alarm history
(most recent alarm)
Occurrence time of alarm that occurred in past
Note : The latest alarm number is in code 0030.
0040 Input signal status 0
Reads the statuses (0 or 1) of the input
signals.
bit 0 to bit F indicate the statuses OFF/ON (0/1) of the
corresponding input signals.
The statuses will be indicating external I/O when the parameter
No.116, No. 117 and No. 118 are changed to external I/O.
bitF bit0
bit0: SON bit4: LSP bit8: MOR bitC: DI2
bit1: ST1 bit5: LSN bit9: COR bitD: DI3
bit2: ST2 bit6: MD0 bitA: DI0 bitE: DI4
bit3: bit7: STP bitB: DI1 bitF: STS
0041 Input signal status 1
Reads the statuses (0 or 1) of the input
signals.
bit 0 to bit F indicate the statuses OFF/ON (0/1) of the
corresponding input signals.
The statuses will be indicating external I/O when the parameter
No. 116, No. 117 and No. 118 are changed to external I/O.
bitF bit0
bit0: PSR bit4: bit8: CDP bitC:
bit1: SPR bit5: bit9: bitD:
bit2: bit6: TL1 bitA: CSL bitE:
bit3: bit7: PC bitB: INC bitF:
0042 Input signal status 2
Reads the statuses (0 or 1) of the input
signals.
bit 0 to bit F indicate the statuses OFF/ON (0/1) of the
corresponding input signals.
The statuses will be indicating external I/O when the parameter
No. 116, No. 117 and No. 118 are changed to external I/O.
bitF bit0
bit0: bit4: bit8: bitC:
bit1: bit5: bit9: bitD:
bit2: bit6: bitA: RES bitE:
bit3: bit7: bitB: bitF: