Specifications
16
BCN-B11127-478*
Device #
Signal name Description
1 station
occupied
2 stations
occupied
Note
Temporary
stop
Turning RY7 from “0” (OFF) to “1” (ON) and keeping it in that status
for longer than 5ms suspends operation. Turning the start signal RY1
or RY2 from “0” (OFF) to “1” (ON) again resumes operation from where
it stopped.
RYn7 RYn7
1
Monitor output
execution
demand
Turning RY8 to “1” (ON) sets the following data/signals. At the same
time, RX8 turns to “1” (ON). While RY8 is “1” (ON), the monitor values
are always updated.
1) When 1 station is occupied
Remote register RW
Rn
: Data requested by monitor 1 (RW
Wn
)
Remote register RW
Rn+1
: Data requested by monitor 2 (RW
Wn+1
)
Remote register RW
Rn+2
: Normal or error answer code
2) When 2 stations are occupied
Remote register RW
Rn
: Lower 16 bits of data requested by monitor 1
(RW
Wn
)
Remote register RW
Rn+1
: Upper 16 bits of data requested by monitor 1
(RW
Wn
)
Remote register RW
Rn+5
: Lower 16 bits of data requested by monitor 2
(RW
Wn+2
)
Remote register RW
Rn+6
: Upper 16 bits of data requested by monitor 2
(RW
Wn+2
)
Remote register RW
Rn+2
: Normal or error answer code
RYn8 RYn8
Instruction code
execution
demand
Turning RY9 to “1” (ON) executes the processing corresponding to the
instruction code set to the remote register RW
Wn+2
.
After completion of instruction code execution, a normal or error
answer code is set to RW
Rn+2
. At the same time, RXD turns to “1” (ON).
RYn9 RYn9
Position block #
selection (bit0)
RYnA RYnA
1,2
Position block #
selection (bit1)
RYnB RYnB
1,2
Position block #
selection (bit2)
RYnC RYnC
1,2
Position block #
selection (bit3)
RYnD RYnD
1,2
Position block #
selection (bit4)
RYnA, RYnB, RYnC, RynD and RYnE are combined to choose the
position table #. Total point table number are up to 31 points.
Point table# RYnE RYnD RYnC RYnB RYnA
1 0 0 0 0 1
2 0 0 0 1 0
3 0 0 0 1 1
4 0 0 1 0 0
: : : : : :
29 1 1 1 0 1
30 1 1 1 1 0
31 1 1 1 1 1
RYnE RYnE
1,2
Synchronous
operation start
Turning RYF to “1” (ON) executes the processing synchronous
operation.
RYnF RYnF
Reset Keeping this signal “1” (ON) for longer than 20ms deactivates any of
the following alarms. The base circuit is off while the signal is “1” (ON).
Indication Name
AL.10
AL.24
AL.31
AL.32
AL.33
AL.35
AL.42
Under voltage
Ground fault
Over speed
Over current
Over voltage
Command pulse
frequency alarm
Feedback alarm
Indication Name
Main circuit
device overheat
Servo motor
overheat
Error excessive
CC-Link alarm
RS-232C alarm
RS-422 alarm
AL.45
AL.46
AL.52
AL.8D
AL.8E
AL.8F
RY(n+1)A RY(n+3)A
1
Note1: These signals may be used as either the CC-Link or CN1A/CN1B external input signals. Make selection in parameter No. 116 to
118.
Note2: No need of external wiring when automatic turn on function was enabled in parameter No. 84 to 86.