(2) Extension cable specifications
The list below describes the specifications of the extension cables which can
be used.
Type
Item
QC05B QC06B QC12B QC30B QC50B QC100B
Cable length[m(ft.)] 0.45(1.48) 0.6(1.97) 1.2(3.94) 3.0(9.84) 5.0(16.40) 10.0(32.81)
Application
Connection between the main base unit and extension base unit,
or connection between the extension base units.
Mass [kg] 0.15 0.16 0.22 0.40 0.60 1.11
POINT
When the extension cables are used in combination, limit the overall length of the
combined cable to 13.2m (43.31ft.).
(3) Names of parts of the base unit
Names of parts of the base unit are described below.
(a) Main base unit (Q35DB, Q38DB, Q312DB)
I/O11
OUT
I/O1 1
I/O1 0
I/O9I/O8
I/O6
I/O5
I/O4
I/O3I/O2
I/O1
I/O0CPU I/O7
Q312DB
5) 4)
3
)
1)
2)
POWER
No. Name Application
1)
Extension cable
connector
Connector for connecting an extension cable (for signal communications with the
extension base unit)
2) Base cover
Protective cover of extension cable connector. Before an extension cable is connected,
the area of the base cover surrounded by the groove under the word "OUT" on the base
cover must be removed with a tool such as nippers.
3) Module connector
Connector for installing the Q series power supply module, CPU module, Motion module,
I/O modules, and intelligent function module.
To the connectors located in the spare space where these modules are not installed,
attach the supplied connector cover or the blank cover module (QG60) to prevent entry of
dirt.
4) Module fixing screw hole Screw hole for fixing the module to the base unit. Screw size: M3 12
5) Base mounting hole Hole for mounting this base unit onto the panel of the control panel (for M4 screw)
(Note): It is impossible to mount the main base unit by DIN rail when using the Motion CPU module. Doing so could result in
vibration that may cause erroneous operation.