Instruction manual

2 - 51
2 SYSTEM CONFIGURATION
POINTS
(1) The Q61P-A1 is dedicated for inputting a voltage of 100VAC.
Do not input a voltage of 200VAC into it or trouble may occur on the Q61P-A1.
Power
module type
Supply power voltage
100VAC 200VAC
Q61P-A1 Operates normally.
Power supply module causes
trouble.
Q61P-A2
Power supply module does
not cause trouble.
CPU module cannot be
operated.
Operates normally.
(2) The Q63P is dedicated for inputting a voltage of 24VDC.
Do not input a voltage of except 24VDC into it or trouble may occur on the Q63P.
(3) Q64P automatically switches the input range 100/200VAC.
Therefore, it is not compatible with the intermediate voltage (133 to 169VAC).
The CPU module may not operate normally if the above intermediate voltage is
applied.
(4) Ensure that the earth terminals LG and FG are grounded.
(Ground resistance :
100
or loss)
Since the LG terminal has a half of the input voltage, touching this terminal may
result in an electric shock.
(5) When the Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P, Q64P or Q64PN is loaded on
the extension base unit, a system error cannot be detected by the ERR terminal.
(The ERR terminal is always OFF.)