Instruction manual
2 - 48
2 SYSTEM CONFIGURATION
POINTS
(Note-4): Inrush current
When power is switched on again immediately (within 5 seconds) after
power-off, an inrush current of more than the specified value (2ms or less)
may flow. Reapply power 5 seconds after power-off.
When selecting a fuse and breaker in the external circuit, take account of
the blow out, detection characteristics and above matters.
(Note-5): During the operation, do not allow the input voltage to change from
200VAC level (170 to 264VAC) to 100VAC level (85 to 132VAC).
If changed, the POWER LED turns OFF and the system operation stops.