Instruction manual
5 - 1
5
5 START-UP PROCEDURES
5. START-UP PROCEDURES
5.1 Check Items Before Start-up
Table 5.1 Check items before start-up
Part name Confirmation Items Check Reference
Main base unit/
Extension base unit
(1) Check that the main base unit is Q35DB, Q38DB or Q312DB.
2.5.3
(2) Check that the model name of module is correct.
2.3
(3) Check that the installation order is correct.
2.1.4
(4) Check that the damage for installed modules.
(5) Check that the modules are installed correctly.
4.1.3
(6) Check for looseness, rattling or distorted installation.
4.1.1
(7) Check that the module fixing screw tightening torque is as specified.
(8) Check that the total I/O points of I/O modules and intelligent function
modules do not exceed the I/O points of the CPU module.
Refer to the
"Q173D(S)CPU/
Q172D(S)CPU Motion
controller Programming
Manual(COMMON)"
Power supply module
(1) Check that the model name of power supply modules is correct.
2.5.2
(2) Check that the wire sizes of cables are correct.
4.5.1
(3) Check that the power line is wired correctly.
(4) Check that FG and LG are wired correctly.
4.5.2
(5) Check that the terminal screws are tightened correctly.
(6) Check that the terminal screws are tightening torque is as specified.
4.1.1
(7) Check that the 100VAC, 200VAC and 24VDC wires are twisted as
closely as possible respectively and run in the shortest distance.
4.5.1
(8) Check that cables are not binded with 100VAC, 200VAC and
24VDC wires or run close to the power wires.
(9) Check the grounding of the earth terminal FG and LG.
4.5.2
PLC CPU module
(1) Check that the model name of PLC CPU modules is correct.
2.1.4
2.3
(2) Check that the modules are installed to CPU slot or I/O slot 0 to 2 of
the main base unit.
2.1.4
Q173D(S)CPU/
Q172D(S)CPU
Motion CPU module
(1) Check that the Q173HCPU(-T)/Q172HCPU(-T)/Q173CPUN(-T)/
Q173CPUN(-T)/Q173CPU/Q172CPU is not used.
2.1.4
(2) Check that the modules are installed to I/O slot 0 to 2 of the main
base unit.
(3) Check that the module fixing screws are tightened correctly.
4.1.1
(4) Check that the forced stop input is wired correctly.
3.2
(5) Check that the battery is installed.
(6) Check that the battery cables are connected correctly.
QD
4.2.2
(7) Check that the battery lead connector is connected correctly.
QDS
4.3
(8) Check that the built-in interface in Motion CPU is wired correctly.
QDS
2.5.1
(9) Check that the manual pulse generator/incremental synchronous
encoder is wired correctly.
QDS