User`s manual

2 - 34
2 SYSTEM CONFIGURATION
(3) Selection of the power supply module
The power supply module is selected according to the total of current
consumption of the I/O modules, intelligent function module, and peripheral
devices supplied by its power module. (Select the power supply module in
consideration of the current consumption of the peripheral device connected to
the Q170ENC, MR-HDP01 etc.)
5VDC internal current consumption of shared equipments with PLC might be
changed. Be sure to refer to the PLC Manuals. .
(a) Calculation example of power supply selection
<System configuration (Q173DCPU use)>
Q38DB
Q173D
CPU
QY10 QY10Q03UD
CPU
Q61P
MR-HDP01
MR-HDP01
Q170ENC
QX40 QX40 Q173DPXQ172DLX Q172DEX
• 5VDC current consumption of each module
Q03UDCPU : 0.33 [A] Q170ENC : 0.20 [A]
Q173DCPU : 1.25 [A] Q173DPX : 0.38 [A]
QX40 : 0.05 [A] MR-HDP01 : 0.06 [A]
Q172DLX : 0.06 [A] QY10 : 0.43 [A]
Q172DEX : 0.19 [A] Q38DB : 0.228 [A]
• Power consumption of overall modules
I
5V = 0.33 + 1.25 + 0.05
2 + 0.06 + 0.19 + 0.20 + 0.38 + 0.06
2 +
0.43
2 + 0.228 = 3.718[A]
Select of the power supply module (Q61P (100/240VAC) 6A) according to
this internal current consumption 3.718[A].
(Note) : Configure the system in such a way that the total current
consumption at 5VDC of all the modules is less than the
allowable value.