Specifications
2. M-NET control
DATA U10
4 - 11SYSTEM DESIGN
S.D. S
2-3. System configuration restrictions
For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
B) Maximum 2 remote controllers for 1 Group;
*MA/ME remote controllers cannot be present together in 1group.
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.
E) System controller is connectable when connecting to TB7 of the Outdoor unit, if the transmission power is supplied
by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-B.
2-3-1. Common restrictions for the CITY MULTI system
*RC: Remote Controller
Table 2-3-1 The equivalent power consumption
Transmission Booster
25
PAC-SF46EPA
Power supply unit Expansion controller
5
PAC-SC51KUA
6
PAC-YG50ECA
BM ADAPTER
6
BAC-HD150
Outdoor unit
12
Connection TB3 andTB7 total
Table 2-3-2 The equivalent power supply
With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the air-
conditioner system to ensure proper system communication according to 2-3-2-A.
2-3-2-A) If the total power consumption reaches 12, a PAC-SF46EPA should be set.
2-3-2. Ensuring proper communication power for M-NET
In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY and Controllers, the transmission
power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the
power consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply
capability index of others are listed at Table 2-3-1 and Table 2-3-2.
System example
LOSSNAY
unit
LOSSNAY
unit
Outdoor unit
M-NET
0201
(Indoor units sized P72 and 96 are counted as 7);
if the total equivalent transmission power consumption reaches 12.
N1
N3
N2
Transmission booster (No.1) should be used,
1.The total equivalent transmission power consumption
should not exceed 25.
Within N2, conditions 1 should be followed.
N4
Within N4, the total equivalent transmission
power consumption should not exceed 25.
TB7 TB3
TB7 TB3
if the total equivalent transmission power consumption reaches 5.
Transmission booster (No.2) should be used,
PAC-SF46EPA
TRANSMISSION BOOSTER
3.4kg
220-240V:0.7A ~/N
WEIGHT
POWER RATING
MODEL
MADE IN JAPAN
50
UP
PAC-SF46EPA
TRANSMISSION BOOSTER
3.4kg
220-240V:0.7A ~/N
WEIGHT
POWER RATING
MODEL
MADE IN JAPAN
50
UP
Transmission
booster
(No.1)
Transmission
booster
PAC-SF46EPA
(No.2)
System Controller
6
GB-50ADA-A
Power supply unit
PAC-SC51KUA
24VDC
Centralized controller
(AG-150A-A)
CENTRALIZED CONTROLLER AG-150A
*To wire PAC-YT53CRAU, use a wire with a diameter of 0.3 mm
2
[AWG22]
LOSSNAY
remote controller
LOSSNAY
remote controller
BC
controller
Indoor unit
PWFY
ME Remote
controller/Adapter
17 622 0 1 5 0 1/4 1/2
Sized
P06-P54
Sized
P72, 96
P36NMU-E-BU
CMB
P36NMU-E-AU
LOSSNAY
LGH-RX-EPEFY-AF1200
CFMR
P72NMU-E-AU
MA RC.
PAC-YT53CRAU
PAR-FA32MA
PZ-41SLB
PZ-60DR-E
PZ-52SF
PAC-YG60MCA
PAC-YG66DCA
PAC-YG63MCA
PAR-U01MEDU
PAC-IF01AHC-J
Centralized
Remote
controller
1/2 1
1/2 2
AG-150A-A
EB-50GU-A
ON/OFF
controller
PAC-YT40ANRA CMS-MNF-B CMS-MNG-E
MN Converter
M-NET
Interface/Converter
30 0
GB-24A LMAP04U-E
BAC-HD150
MAC-333
PAC-SF83MA-E
4
TC-24B
ME remote
Controller
ME remote
Controller