Specifications
2. M-NET control
DATA U10
SYSTEM DESIGN 4 - 10
S.D. S
2-2. Transmission cable specifications
Type of cable
Cable size
Remarks
Sheathed 2-core cable (unshielded)
CVV
Shielding wire (2-core)
CVVS, CPEVS or MVVS
Transmission cables ME Remote controller cables
CVVS, MVVS: PVC insulated PVC jacketed shielded control cable
CPEVS: PE insulated PVC jacketed shielded communication cable
*1 To wire PAC-YT53CRAU, use a wire with a diameter of 0.3 mm
2
 [AWG22]
*2 The use of cables 0.75 mm
2
 [AWG18] or greater is recommended for easy 
 handling. 
CVV: PV insulated PVC sheathed control cable
—
Max length : 200m [656ft]
(L
i
)
MA Remote controller cables
When 10m [32ft] is exceeded, use cables with
the same specification as transmission cables.
More than 1.25 [AWG16]
2 
0.3 1.25 [AWG22 16]
*1 *2
2 
0.3 1.25 [AWG22 16]*2