Specifications
2. M-NET control
DATA U10
4 - 9SYSTEM DESIGN
S.D. S
2. M-NET control
2-1. Transmission cable length limitation
Applicable to Outdoor as follows
PUMY-P-NHMU
PUMY-P-NKMU
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft] 1.25mm
2
[AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1, L3+L4, L6, L2+L6, L7 <=200m[656ft] 1.25mm
2
[AWG16] or thicker
Max. length from MA to Indoor a1+a2, a1+a2+a3+a4 <=200m[656ft] -
24VDC to AG-150A-A n <=50m[164ft] 0.75-2.0 mm
2
[AWG18-14]
Applicable to Outdoor as follows
PUMY-P-NHMU
PUMY-P-NKMU
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable)
L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7
<=500m[1640ft] 1.25mm
2
[AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1, L3+L4, L6, L2+L6, L7, L3+L5 <=200m[656ft] 1.25mm
2
[AWG16] or thicker
Max. length from ME to Indoor e1,e2,e3,e4 <=10m[32ft] *1 0.3-1.25 mm
2
[AWG22-16] *1
24VDC to AG-150A-A n <=50m[164ft] 0.75-2.0 mm
2
[AWG18-14]
*1. If the length from ME to Indoor exceed 10m, use 1.25 mm
2
[AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.
OC: Outdoor unit; IC: Indoor unit; MA: MA remote controller
OC: Outdoor unit; IC: Indoor unit; ME: ME remote controller
M1 M2
M1 M2 S
TB7
TB3
IC
(51)
M1 M2 12S
TB5 TB15
12
TB15
12
TB15
12
TB15
12
TB15
12
TB 15
12
TB15
MA
(01)
IC
M1 M2 S
TB5
(02)
IC
M1 M2 S
TB5
(04)
IC
M1 M2 S
TB5
(03)
IC
M1 M2 S
TB5
(05)
IC
M1 M2 S
TB5
(07)
IC
M1 M2 S
TB5
(06)
L
2
L
1
MA
MA
OC
M1 M2
M1 M2 S
TB7
TB3
(52)
OC
a1
a3
L
3
L
4
a2
AB
AB
AB
a2
a1
a1
MA
AB
a4
a2
Group1 Group3 Group5
Shielded
wire
S
Power Supply Unit
ABS
AG-150A-A
PAC-SC51KUA
L
6
L
7
AB
V+V-FG
n
V+V-FG
M1 M2
M1 M2 S
TB7
TB3
(52)
OC
M1 M2
M1 M2 S
TB7
TB3
IC
Group1 Group3
Group5
(51)
M1 M2 S
TB5
ME
(01)
IC
M1 M2 S
TB5
(02)
IC
M1 M2 S
TB5
(04)
IC
M1 M2 S
TB5
(03)
IC
M1 M2 S
TB5
(05)
IC
M1 M2 S
TB5
(07)
IC
M1 M2 S
TB5
(06)
L
2
L
1
(101)
ME
(105)
ME
(103)
ME
(155)
OC
Shielded
wire
ABS
ABS
AG-150A-A
L
3
L
6
L
7
L
4
L
5
e2
e3
e4
e1
AB
AB AB
AB
V+V-FG
n
V+V-FG
Power Supply Unit
PAC-SC51KUA
2-1-2. Using ME Remote controller
2-1-1. Using MA Remote controller
ME remote controller refers to Smart ME controller.
NOTE
Do not daisy-chain remote controllers.
MA remote controller refers to Simple MA remote controller and wireless remote controller.
NOTE
Do not daisy-chain remote controllers.