Specifications

2. M-NET control
DATA U10
4 - 23SYSTEM DESIGN
S.D. S
2-4-3-10. BM ADAPTER + PAC-YG50ECA (Expansion controller)
HUB
Outdoor unit
Heat source unit
(PUHY, PUMY, PQHY)
Outdoor unit
Heat source unit
(PUHY, PUMY, PQHY)
Outdoor unit
Heat source unit
(PUHY, PUMY, PQHY)
51
DipSW2-1
*5
ON
TB3
01 02 03
101 151 103
Outdoor unit
Heat source unit
(PURY, PQRY)
54
DipSW2-1
*5
ON
TB3
TB3
55 04 05 06
104 105 106
107 108 158
BC controller
Outdoor unit
Heat source unit
(PURY, PQRY)
51
DipSW2-1
*5
ON
TB3
TB7
TB7
TB7
TB7
TB7
TB7
52 01 02 03
101 151 103
BC controller
57
DipSW2-1
*5
ON
07 08
09
107 108
54
DipSW2-1
*5
ON
TB3
04 05 06
104 105 106 156
Outdoor unit
Heat source unit
(PURY, PQRY)
57
DipSW2-1
*5
ON
TB3
58 07 08 09
BC controller
PAC-YG50ECA*3
000
000
LOSSNAY
Group 1 Group 2
Group 3 Group 4 Group 5
Group 6 Group 7
Group 3 Group 4 Group 5
Group 1 Group 2
Group 6 Group 7
BM ADAPTER
*1
can transmit max. 150 indoor units via expansion controllers (PAC-YG50ECA).
When the dual-set-point function is used, no expansion controllers can be connected, and only up to 50 units can be controlled
from each BAC-HD150.
BM ADAPTER
PAC-YG50ECA*3
PAC-YG50ECA*3
AG-150A-A*2
24VDC TB3
Power supply unit
(PAC-SC51KUA)
LAN
000
LAN2
LAN1
BACnet
®
*1 BM ADAPTER (Ver. 2.00 or later) supports the expansion controller.
*2 AG-150A-A (Ver. 2.30 or later) supports the BM ADAPTER.
*3 PAC-YG50ECA (Ver. 1.30 or later) supports the BM ADAPTER.
*4 Consult your dealer for restrictions when connecting both AG-150A-A and BM ADAPTER to PAC-YG50ECA.
*5 On PUHY and PURY (YKM) units, set DipSW5-1 to ON instead of DipSW2-1.
NOTE:
It is not necessary to connect the M-NET transmission line to the TB3 on BM ADAPTER.
Leave the power jumper of BM ADAPTER connected to CN41.