Specifications

2. M-NET control
DATA U10
SYSTEM DESIGN 4 - 16
S.D. S
Outdoor unit
(PUMY)
Indoor unit
MA R/C MA R/C MA R/C
(Main) (Sub)
MA R/C
00
DipSW2-1
OFF
TB3
MA R/C: PAC-YT53CRAU
00 00 00 00 00
TB15
TB5 TB5TB5 TB5 TB5
MA R/C
TB15 TB15 TB15 TB15
Group 2Group 1 Group 3 Group 4
2-4-3-1. Example : Basic (No address setting)
2-4-3. System example
Main R/C: PAR-U01MEDU
Sub R/C: PAR-U01MEDU
Indoor unit
Sub
R/C
Main
R/C
Main
R/C
Main R/C
51
DipSW2-1
OFF
TB3
01 02 03 04 05
153103101 105
Group 1 Group 2 Group 3
2-4-3-2. Example : Basic , Sub/main ME remote controller
Outdoor unit
(PUMY)
CN40 CN41
CN40 CN41
Factory setting
Original switch setting of the outdoors, indoors, controllers, LM-AP, and BM ADAPTER at shipment is as follows.
Outdoor unit : Address: 00, CN41: ON (Jumper), DipSW2-1: OFF
Indoor unit : Address: 00
ME remote controller : Address: 101
LM-AP : Address: 247, CN41: ON (Jumper), DipSW1-2: OFF
BM ADAPTER : Address: 000, CN41: ON (Jumper)