ML-KP09NA.TH Submittal

D: In. (mm) 11-1/4 (285)
H: In. (mm) 21-5/8 (550)
Package Dimensions
W: In. (mm) 37 (940)
D: In. (mm) 14-15/16 (380)
H: In. (mm) 24-13/16 (630)
Unit Weight Lbs. (kg) 81 (37)
Package Weight Lbs. (kg) 88 (40)
Outdoor Unit Operating
Temperature Range
Cooling Air T
emp (Maximum / Minimum)* °F 115 / 14
Cooling Thermal Lock-out / Re-start Temperatures** °F -1 / 3
Heating Air Temp (Maximum / Minimum) °F 75 / -4
Heating Thermal Lock-out / Re-start Temperatures** °F -9 / -4
Refrigerant
Type R410A
Charge Lbs, oz 2, 5
Piping
Gas Pipe Size O.D. (Flared) In.(mm) 3/8 (9.52)
Liquid Pipe Size O.D. (Flared) In.(mm) 1/4 (6.35)
Maximum Piping Length Ft. (m) 65
Maximum Height Difference Ft. (m) 40
Maximum Number of Bends 10
Notes
AHRI Rated Conditions
(Rated data is
determined at a fixed
compressor speed)
1
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
Conditions
4
Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB
5
Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB
*Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
Notes
AHRI Rated Conditions
(Rated data is
determined at a fixed
compressor speed)
1
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
Conditions
4
Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB
*Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
SPECIFICATIONS: MLZ-KP09NA & SUZ-KA09NA2
Specifications are subject to change without notice. © 2019 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.