User Guide

Specications are subject to change without notice. © 2017 Mitsubishi Electric US, Inc.
Notes:
SPECIFICATIONS: MXZ-3C24NAHZ2
Indoor Unit Type SEER EER HSPF
COP @
47°F
COP
@ 17°F
Non-ducted
(06 + 06 + 09)
19.0 13.5 10.0 4.25 2.53
Ducted and
Non-ducted
17.3 11.75 9.5 4.03 2.52
Ducted
(09 + 09 + 09)
15.5 10.0 9.0 3.80 2.51
Outdoor
Cooling D.B. 14 to 115° F [ D.B. −10 to 46° C]*1
Heating W.B. -13 to 65° F [ W.B. −25 to 18° C ]
*1. D.B. 5 to 115° F [ D.B. −15 to 46° C ], when an optional Air Outlet Guide
is installed.
Minimum of two Indoor Units must be connected to the MXZ-3C24NAHZ2.
Minimum installed capacity cannot be less than 12,000 Btu/h.
Total connected capacity must not exceed 130% of outdoor unit capacity.
System can operate with only one Indoor Unit turned on.
Information provided at 208/230V.
For Reference:
- MXZ-C Technical & Service Manual for detailed specications and additional information per Indoor Unit Combination.
- MXZ Series Multi-Zone Indoor/Outdoor Combination Table for allowed unit combinations.
Only 1 MVZ may be used on any system.
When an MVZ is connected, total connected capacity must be 100% or less.
When an MVZ is connected, no P-Series indoor units can be used (PCA, PLA, or PEAD).
ENERGY EFFICIENCIES:
NOTES:
OPERATING RANGE:
MVZ CONNECTION RULES: