Installation manual

4
Wall
Outdoor
side
2-2. HOLE DRILLING
1) Determine the wall hole position.
2) Drill a dia. 65 mm hole (dia. 75 mm for KA50). The outdoor side
should be 5 to 7 mm lower than the indoor side.
3) Insert wall hole sleeve (C).
2-1. FIXING OF INDOOR UNIT MOUNTING BRACKET
• Findastructuralmaterial(suchasastud)inthewallandxbracket(7)horizontallywithxingscrews(8).
• Topreventbracket(7)fromvibrating,besuretoinstallthexingscrewsintheholesindicatedby[->]intheillustration.Foraddedsupport,xingscrews
may also be installed in other holes.
2. INDOOR UNIT INSTALLATION
FOR RIGHT DOWNWARD OR LEFT DOWN-
WARD PIPING
(Thefollowinggureisaviewofthebottomof
the indoor unit from above.)
FOR REAR OR LEFT-REAR PIPING
(Thefollowinggureisafrontview
of the indoor unit installation location.)
FOR LEFT PIPING FOR RIGHT PIPING
When the unit is
installed on the wall.
When the unit is
installedontheoor.
HOLE POSITIONS
ø65mm (KA25/35)
ø75mm (KA50)
5 - 7 mm
2-3. INDOOR UNIT PREPARATION
Remove the front panel of the indoor unit.
1) Push the 2 locations marked “PUSH” on the upper part of the front
grille until a “click” is heard.
2) Open the front grille toward you.
3) Remove the 2 screws.
4) Grasp the rear horizontal vane at the upper air outlet, and open it.
5) Push the 3 locations on the top of the front panel, and then pull the
upper part of the front panel toward you.
6) Remove the front panel while lifting it up (slightly).
* The front panel can be removed without opening the damper of the
lower air outlet.
*
Do not open the damper
of the lower air outlet.
Front horizontal
vane
Rear horizontal
vane
Front panel
Front panel
Push
Indoor unit
Indoor unit
JG79A144H05.indd 4 2011/06/22 16:01:19