(8) Selection example of wires
To comply with the UL/C-UL Standard, use UL-approved copper wires rated at 60/75
(140/167 ) for
wiring.
The following table shows the wire sizes [AWG] and the crimping terminal symbols rated at 60
(140 ).
The sizes and the symbols rated at 75
(167 ) are shown in the brackets.
(Note 3) Wires [mm
2
]
Servo amplifier
L
1
L
2
L
3
L
11
L
21
U
V W
P
1
P
2
P
P
2
C
MR-J3-10B(1)-RJ006 to 40B(1)-RJ006
60B-RJ006
70B-RJ006
MR-J3-100B-RJ006 200B-RJ006
14(14) (Note 4) 14(14)
MR-J3-350B-RJ006 12(12)
16(16)
12(12)
14(14)
(Note 1) MR-J3-500B-RJ006 10(10): a(a) 10(10): a(a) 14(14): g(g)
(Note 1) MR-J3-700B-RJ006 8(8): b(b)
16(16): h(h)
8(8): b(b) 12(12): a(a)
(Note 1) MR-J3-11KB-RJ006 6(6): c(c) 4(4): d(c)
(Note 1) MR-J3-15KB-RJ006 4(4): d(d) 16(16): g(g) 2(3): e(d)
10(10): j(j)
(Note 1) MR-J3-22KB-RJ006 1/0(1): f(p) (1): (p) 10(10): k(k)
MR-J3-60B4-RJ006
MR-J3-100B4-RJ006 14(14) 16(16) 14(14) 14(14)
MR-J3-200B4-RJ006
MR-J3-350B4-RJ006 14(14): g(g) 14(14): g(g)
(Note 1) MR-J3-500B4-RJ006 16(16): h(h) 10(12): a(a) 14(14): g(g)
(Note 1) MR-J3-700B4-RJ006
10(12): a(a)
10(10): a(a)
(Note 1) MR-J3-11KB4-RJ006 8(10): l(j) 8(8): l(l) 12(12): j(j)
(Note 1) MR-J3-15KB4-RJ006 6(8): c(l) 16(16): g(g) 4(6): d(c) 10(10): j(j)
(Note 1) MR-J3-22KB4-RJ006 6(6): m(m) 4(6): n(m) 10(10): k(k)
Wires [mm
2
]
Servo amplifier
B1
B2 BU BV BW OHS1 OHS2
MR-J3-10B(1)-RJ006 to 40B(1)-RJ006
60B-RJ006 70B-RJ006
MR-J3-100B-RJ006 200B-RJ006
MR-J3-350B-RJ006
(Note 1) MR-J3-500B-RJ006
(Note 1) MR-J3-700B-RJ006 (Note 2) 14(14) (Note 2) 16(16)
(Note 1) MR-J3-11KB-RJ006
(Note 1) MR-J3-15KB-RJ006 14(14) 16(16)
(Note 1) MR-J3-22KB-RJ006
MR-J3-60B4-RJ006
16(16)
MR-J3-100B4-RJ006
MR-J3-200B4-RJ006
MR-J3-350B4-RJ006
(Note 1) MR-J3-500B4-RJ006
(Note 1) MR-J3-700B4-RJ006 (Note 2) 14(14) (Note 2) 16(16)
(Note 1) MR-J3-11KB4-RJ006
(Note 1) MR-J3-15KB4-RJ006 14(14) 16(16)
(Note 1) MR-J3-22KB4-RJ006
Note 1. To connect these models to a terminal block, be sure to use the screws that come with the terminal block.
2. For the servo motor with a cooling fan.
3. Alphabets in the table indicate crimping tools. Refer to the following table for the crimping terminals and crimping
tools.
4. To wire the servo amplifier and a HF-MP
KP servo motor, use the MR-PWS1CBL (option). To extend the wiring,