Instruction manual

6 - 18
6. PARAMETERS
Classification
No.
Symbol
Name and Function
Initial
Value
Unit
Setting range
PS06 LB2
Linear servo motor control speed deviation error detection level
Used to set the speed deviation error detection level of the linear
servo motor control error detection. When the difference between the
model feedback speed and the feedback speed is bigger than this
setting value, the linear servo motor control error is detected (42).
(Refer to Section 5.6.1)
1000 mm/s 1 to 5000
PS07 LB3 Linear servo motor control thrust deviation error detection level
Used to set the thrust deviation error detection level of the linear
servo motor control error detection. When the difference between the
command thrust and the feedback thrust is bigger than this setting
value, the linear servo motor control error is detected (42).
(Refer to Section 5.6.1)
100 % 1 to 1000
PS08 *LIT3
Linear function selection 3
The magnetic pole detection method can be selected. (Refer to
Section 5.2.6)
Selection of magnetic pole
0: Detection method
1: Position detection method
2: Current detection method
010
0010h Refer to the
name and
function
column
PS09 LPWM
Magnetic pole detection voltage level
Used to set the direct current exciting voltage level during the
magnetic pole detection. When the overload alarm (50 and 51) or
overcurrent alarm (32) occurs, set the smaller value. When the initial
magnetic pole detection error occurs during the magnetic pole
detection, set the bigger value. (Refer to Section 5.2.3)
30 % 0 to 100
PS10 LFH
At magnetic pole detection current detection method Identification
signal frequency
Used to set the identification signal frequency of the magnetic pole
detection current detection method. This parameter is made valid
when parameter No.PS08 is set to "
1" or " 2". The upper
limit of the setting value must be under half of the speed loop
response frequency. (Refer to Section 5.2.6)
5 Hz 1 to 500
PS11 LIDH
At magnetic pole detection current detection method Identification
signal amplitude.
Used to designate the identification signal amplitude of the magnetic
pole detection current detection method.This parameter is made valid
when parameter No.PS08 is set to "
1" or " 2". When the
overload alarm (50 and 51) occurs, set the smaller value. (Refer to
Section 5.2.6)
100 % 50 to 100
PS12
500
PS13
0000h
PS14
0000h
PS15
0000h
PS16
0000h
PS17
0000h
PS18
0000h
PS19
0000h
PS20
0000h
PS21
0000h
PS22
0000h
Special setting parameters
PS23
For manufacturer setting
Do not change these values by any means.
0000h