5. OPERATION AND FUNCTIONS
5.6 Functions
5.6.1 Linear servo control error detection function
POINT
For the linear servo control error detection function, the position and speed
deviation error detections are enabled as factory-set. (Parameter No. PS04:
3)
If the linear servo control gets unstable for some reasons, the linear servo motor may not operate properly. The
protective function for detecting this before happens and stopping the operation is the linear servo control error
detection function.
As the linear servo control error detection function, there are three types of detection methods: speed
deviation, position deviation and thrust deviation. An error is detected when each error detection function is
enabled with the setting of the parameter No. PS04 (Linear function selection 2). The detection level can be
changed with the parameter Nos. PS05, PS06 and PS07.
Servo amplifier internal value
1) Model feedback position [mm]
3) Model feedback speed [mm/s]
5) Command thrust [%]
Linear encoder
2) Feedback position [mm]
4) Feedback speed [mm/s]
6) Feedback thrust [%]
Linear servo motor
Linear encode
r
Servo amplifier
Figure 5.1 Outline of linear servo control error detection function
(1) Position deviation error detection
Set the parameter No. PS04 to "
1" to make the position deviation error detection enabled.
1
Position deviation
error detection
Parameter No. PS04
If there is a deviation larger than the setting value (1 to 200mm) of the parameter No. PS05 (Linear servo
control position deviation error detection level) after comparing the model feedback position 1) and the
feedback position 2) in Figure 5.1, the alarm (Linear servo control error detection 42) occurs, and the linear
servo motor stops. The initial value of parameter No. PS05 is 50mm. Change the setting value as necessary.