11. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
Power supply
3-phase
200V or 230VAC
or 3-phase
380 to 480VAC
NFB
MC
Servo amplifier
L
11
L21
L
1
L2
L
3
SK
ON
MC
BC
NPC
RDY
SE
Alarm
output
RDY
output
A
B
C
5m(16.4ft) or less
Operation ready
MC
OFF
EMG
RA2
FR-RC
Ready
Power factor improving reactor
FR-BAL
R/L
1
S/L
2
T/L
3
B
C
RRX
R
SX
S
TX
T
Phase detection
terminals
(Note 1)
Power regeneration
converter FR-RC(-H)
N/
P/
EM1
RA
DOCOM
DICOM
ALM Trouble
(Note 3)
DOCOM
Forced stop
24VDC
P
2
P
1
(Note 4)
(Note 2)
CN3 CN3
(Note 5)
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain
removed, the FR-RC(-H) will not operate.
2. When using servo amplifiers of 5kW and 7kW, always remove the lead of built-in regenerative brake resistor
connected to P terminal and C terminal.
3. When setting not to output Trouble (ALM) with parameter change, configure power supply circuit for turning magnet
contactor off after detecting an occurrence of alarm on the controller side.
4. Always connect P
1
-P
2
(For 11k to 22kW, connect P-P
1
). (Factory-wired.) When using the power factor improving DC
reactor, refer to Section 11.13.
For 400 VAC class, the stepdown transformer is required.