Specifications
39
MITSUBISHI ELECTRI
C
MELSERVO MR-J2S
OPTIONS AND PERIPHERAL EQUIPMENT
BASICS
왎
Noise Filters
왎 Transformers
For complying with the EMC directives of
the European Community regarding
the electromagnetic compatibility, the
servo amplifiers have to be equipped
with a noise filter across the input circuit.
Additionally it has to be installed and
wired according to the EMC directives.
The filter units are designed to reduce
mains conducted RFI emissions to meet
the European standard EN 55022 A/B.
More details are enclosed in the EMC short
reference sheet of the MR-J2S filters.
왎
Brake Resistors
If the regenerative power exceeds the
power of the built-in resistor,
the following listed optional brake resis
-
tors can be used.
Resistor Servo amplifier
Power
capacity [W]
Resistance
(Ω)
Weight
[kg]
Dimensions
(WxHxD)
Order
number
MR-RFH75-40 MR-J2S-10A/B to MR-J2S-70A/B 150 40 0.16 36 x 27 x 90 137279
MR-RFH220-40 MR-J2S-100 A/B 400 40 0.42 36 x 27 x 200 137278
MR-RFH400-13
MR-J2S-200A/B, MR-J2S-350A/B
and MR-J2S-500A/B
600 13 0.73 36 x 27 x 320 137277
MR-RFH400-6,7 MR-J2S-700A/B 600 6.7 0.73 36 x 27 x 320 137275
This auto transformer is used to adapt the
servoamplifiertoa3~400Vpowersupply.
Further, this auto transformer reduces the
harmonics generated by the system and it
protects the servo electronics.
The input voltage is 400 V, the output
voltage is 230 V.
Transformer
Power capacity
[kVA] ([kW])
ED [%]
Input
current [A]
Output
current [A]
Power
dissipation [W]
Weight
[kg]
Order
number
MT 1,3-60
1.3 (0.4)
1.7
60
30
2.02
2.69
3.26
4.27
103
167
7.0 137281
MT 1,7-60
1.7 (0.7)
2.5
60
30
2.61
3.89
4.27
6.28
110
199
10.7 137302
MT 2,5-60
2.5 (1.0)
3.5
60
30
3.80
5.42
6.28
8.78
155
282
16.5 137303
MT 3,5-60
3.5 (2.0)
5.5
60
30
5.30
8.41
8.78
13.80
170
330
22.0 137304
MT 5,5-60 5.5 (3.5) 60 8.26 13.80 243 22.0 137305
MT 7,5-60 7.5 (5.0) 60 11.25 18.82 190 28.0 137306
MT 11-60 11 (7.0) 60 16.40 27.61 280 41.0 137307
Filter Servo amplfier
Power
loss [W]
Rated
current
[A]
Leakage
current
[mA]
Weight
[kg]
Order
number
MF-2F230-007.230
햲
MR-J2S-10A/B to MR-J2S-70A/B 11 7 <9 1.0 140055
MF-3F230-010.230
햲
MR-J2S-100 A/B 16 10 < 0.60 (<32)
햳
2.1 140056
MF-3F230-025.230
햲
MR-J2S-200A/B and MR-J2S-350A/B 33 25 < 0.62 (<36)
햳
2.5 140057
MF-3F230-050.230
햲
MR-J2S-500A/B and MR-J2S-700A/B 31 50 < 0.65 (<72)
햳
3.0 140058
햲
All filters conform to EN55011A at a cable length of 50 m and EN55022B at 20 m.
햳
At normal operation: voltage difference between 2 phases < 3 % / at fault occurrence (value in brackets) : 2 dead phases (worst case)