User`s manual
9
Wrap the coated parts
with a heat contractile
tube.
(10) To make this product conform to the EMC directive and low voltage
instruction, be sure to use the AD75CK type cable clamp (manufactured
by Mitsubishi Electric) for grounding to the control box.
QD75
AD75CK
20cm(7.88inch)
to 30cm(11.82inch)
Inside control box
Using the AD75CK, you can tie four cables of about 7mm (0.28inch)
outside diameter together for grounding.
(11) The influence of noise may be reduced by installing ferrite cores to the
cable connected to the QD75 as a noise reduction technique.
For the noise reduction techniques related to connection with the servo
amplifier, also refer to the instruction manual of the servo amplifier.
(12) If compliance with the EMC directive is not required, the influence of
external noise may be reduced by making the configuration compliant
with the EMC directive.
For the configuration compliant with the EMC directive, refer to Chapter
9 "EMC AND LOW VOLTAGE DIRECTIVES" of the QCPU User's
Manual (Hardware Design, Maintenance and Inspection).