Specifications

4 - 12
Software stroke limit upper limit value
Set the upper limit for the machine's movement range during positioning control.
Software stroke limit lower limit value
Set the lower limit for the machine's movement range during positioning control.
(However, the stroke limit value is ignored during the JOG operation.)
(Machine movement range)
Software stroke
limit lower limit
Software stroke
limit upper limit
Emergency
stop limit switch
OP
Emergency
stop limit switch
Figure 4.6 Software stroke limit upper limit value/lower limit value
(1) Generally, the OP is set at the lower limit or upper limit of the stroke limit.
(2) By setting the upper limit value or lower limit value of the software stroke limit,
overrun can be prevented in the software. However, an emergency stop limit
switch must be installed nearby outside the range.
Command in-position width
This is the value of "positioning address" from which "current feed value" was
subtracted at the position where the command in-position signal (bit 2 of the buffer
memory 817, 917, 1017, and 1117) turns ON.
(It is used as a front-loading signal of the positioning complete signal.)
Position control start
Speed
Command in-position setting value
Command in-position flag