Pulse output mode
Set the pulse output mode to match the servo amplifier being used.
(The QD75 outputs the pulse in negative logic at default.)
(1) PLS/SIGN mode
Forward run and reverse run are controlled with the ON/OFF of the direction sign
(SIGN).
• The motor will run in the forward direction when the direction sign is LOW.
• The motor will run in the reverse direction when the direction sign is HIGH.
Forward run
Move in + direction
Reverse run
Move in - direction
PULSE
SIGN
(2) CW/CCW mode
During forward run, the forward run feed pulse (PULSE F) will be output.
During reverse run, the reverse run feed pulse (PULSE R) will be output.
Forward run Reverse run
PULSE F
PULSE R
(3) A phase/B phase mode (Common for multiple of 4 and multiple of 1)
Forward run and reverse run are controlled with the phase difference of the A
phase (A
φ
) and B phase (B
φ
).
• When the B phase is 90° behind the A phase, the motor will run in the forward
direction.
• When the B phase is 90° ahead of the A phase, the motor will run in the reverse
direction.
(1) For multiple of 4 setting
Forward run
When B phase is 90°
behind A phase
Reverse run
When B phase is 90°
ahead of A phase
(2) For multiple of 1 setting
Forward run
When B phase is 90°
behind A phase
Reverse run
When B phase is 90°
ahead of A phase