Specifications
6 - 23
6.11.1 PLC READY
Project name
X
Always set this program.
SM1039
(RUN, Always ON after 1 scan)
PLC READ
Y
Y0A0
As the READY output condition,
provide an interlock if needed.
M10
6.11.2 Error code display and error reset
(PLC CPU
battery error)
(PLC CPU
battery error)
SM1032
SM1006(PLC CPU battery error)
Y77
X0A8
X0B(Error reset command)
Y0B0
RST
(QD75 error detection)
D106BCDP
Reset of
positioning
start flag
1s clock
K4Y60
Displays the error
code read by the
automatic refresh
G1502
K1
MOVP
U0A\
Demonstration machine operation
Displays the X axis error code that is read from the buffer memory "806" by the
automatic refresh, in BCD code on the digital display.
0
1
0
4
This display example (104) is out
of the hardware stroke limit range.
Error code 3 digits
Y
6F to Y60
Error codes are roughly divided as follows.
Error Code Classification of errors
001 to 009
Fatal error
100 to 199 Common error
200 to 299 Error at OPR or absolute position restoration
300 to 399 Error during JOG operation or inching
operation
500 to 599 Error during positioning operation
800 to 899 I/F (Interface) error
900 to 999 Error during parameter setting range check
Refer to the manual or the error code list of QD75P Help for details.