Specifications

5 - 7
From the previous page
6) The dialog box appears asking whether to
move to the online mode (move to the test
mode) and to initialize the QD75.
Click the Initialize
button to initialize the
QD75 and then move to the test mode.
Parameters and positioning data are not
initialized in this process. The internal data of
the QD75 module is initialized.
7) The dialog box appears confirming that the
QD75 has been successfully changed to
TEST MODE.
Click the OK
button.
8) Check the "External input output signal" status
on the connection check window.
• Upper limit, Lower limit,
Drive unit ready
(Red): ON
• Stop signal, External command
(Gray)
: OFF
9) Check the ON/OFF of "External input output
signal" with the STOP and CHG switches of
the 1-axis demonstration machine.
STOP = Stop signal,
CHG = External command
10) Enter a speed in the text box of "JOG speed"
and press and hold the left button of the
mouse for a few seconds with the mouse
pointer on [FWD] or [RVS].
The JOG operation is performed for the
period of time the left button of the mouse
was pressed.
11) Check how "Current feed value" was changed
and "Feed speed" at the Operation monitor
during the JOG operation.
12) Click the Offline
button. The dialog box
appears asking whether to terminate the test
mode.
Click the Yes
button to terminate the
connection check.
REMARK
The operation check of the upper/lower limit switches (FLS/RLS) can be performed
in the JOG operation.
Perform one of the three following operations to initialize the parameters and the
positioning data.
1) Select and execute "QD75Initialization" with the QD75P in the online mode.
2) Execute the QD75 dedicated instruction "PINIT".
3) Write "1" to the buffer memory "1901".