Type QD75P/QD75D Positioning Module User’s Manual (Hardware) QD75P1, QD75D1 QD75P2, QD75D2 QD75P4, QD75D4 Thank you for buying the Mitsubishi general-purpose programmable logic controller MELSEC-Q Series Prior to use, please read both this manual and detailed manual thoroughly and familiarize yourself with the product.
! SAFETY PRECAUTIONS ! (Always read before starting use) When using this equipment, thoroughly read this manual. Also pay careful attention to safety and handle the module properly. These precautions apply only to this equipment. Refer to the User’s Manual of the CPU module to use for a description of the PLC system safety precautions. These "Safety Precautions" classify the safety precautions into two categories: "DANGER" and "CAUTION".
[WIRING PRECAUTION] DANGER ! Switch all phases of the external power supply off when installing or placing wiring. Not doing so may cause electric shock or damage to the product. CAUTION ! Check the layout of the terminals and then properly route the wires to the module. ! Solder connectors for external device properly. Insufficient soldering may cause malfunction. ! Be careful not to let foreign matter such as sawdust or wire chips get inside the module. These may cause fires, failure or malfunction.
Revisions Print Date Oct., 1999 Feb., 2000 * The manual number is noted at the lower left of the back cover. *Manual Number Revision IB(NA)-0800063-A First edition IB(NA)-0800063-B Addition "Confirmation to EMC directive" Jun., 2001 IB(NA)-0800063-C Modification About Manuals, Conformation to the EMC Directive and Low Voltage Instruction, 2. Performance Specification, 4. Part Identification Nomenclature, 5.Wiring Nov., 2001 IB(NA)-0800063-D Addition 1. Overview, 2. Performance Specifications, 4.
CONTENTS 1. Overview ........................................................................................................1 2. Performance Specifications ...........................................................................2 3. Handling.........................................................................................................3 3.1 Handling Precautions ...............................................................................3 4. Part Identification Nomenclature ..................
1. Overview This manual explains how to handle the Positioning Module, model numbers QD75P1, QD75P2, QD75P4, QD75D1, QD75D2 and QD75D4 (hereinafter collectively referred to as the QD75). After unpacking the QD75, please verify that the corresponding product as listed below is enclosed in the package.
2. Performance Specifications (1) The performance specifications for the QD75P1, QD75P2 and QD75P4 Item Number of axes Maximum output pulse count Maximum connection distance between servos Applicable wire size Applicable connector Number of I/O occupied points 5 V DC current consumption Flash ROM write count Weight Specification QD75P2 2 axes QD75P1 1 axis QD75P4 4 axes 200 kpulse/s 2m (6.56ft) 0.
3. Handling CAUTION ! Use the PLC in an environment that meets the general specifications contained in CPU module User's Manual to use. Using this PLC in an environment outside the range of the general specifications may cause electric shock, fire, malfunction, and damage to or deterioration of the product. ! When installing the module, securely insert the module fixing tabs into the mounting holes of the base module while pressing the installation lever located at the bottom of the module downward.
4. Part Identification Nomenclature (1) Part identification nomenclature (a) For QD75P4 (b) For QD75D4 QD75P4 RUN ERR AX3 AX4 QD75D4 AX1 AX2 AX3 AX4 RUN 1) ERR AX1 AX2 AX3 AX4 AX1 AX2 AX3 AX4 1) AX1 AX2 2) 2) 3) Number Name Number 1) LED Display 3) Differential driver common terminal 2) Name External device connector (The QD75P1, QD75P2, QD75D1 and QD75D2 have the right-hand side connector only.) (2) LED display contents Details of indication QD75 4 RUN ERR.
(3) External device connector signal layout Pin layout B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 Axis 4 (AX4) Pin Signal name No.
5. Wiring DANGER ! Switch all phases of the external power supply off when installing or placing wiring. Not doing so may cause electric shock or damage to the product. 5.1 Wiring Precautions (1) If cables to connect to QD75 absolutely must be positioned near (within 100 mm) the power line, use a general shielded cable. The shield must be grounded on the QD75 side.
Wrap the coated parts with a heat contractile tube. (2) The shielded cable for connecting QD75 can be secured in place. If the shielded cable is not secured, unevenness or movement of the shielded cable or careless pulling on it could result in damage to the QD75 or drive unit or shielded cable or defective cable connections could cause mis-operation of the unit.
5.2 External Interface The internal circuits of interface for connecting external devices to the QD75 are shown by the schematic diagrams in the tables below (for the QD75P1 and QD75D1).
(2) Output (for QD75P1) External wiring Pin number Internal circuit Wiring requirement * Signal name 1A13 Deviation counter clear CLEAR 1A14 Common CLEAR COM 1A15 CW A phase PULSE PULSE F CCW B phase SIGN PULSE R 1A16 1A17 1A18 PULSE COM PULSE COM (3) Output (for QD75D1) External wiring Pin number Internal circuit Wiring requirement * Signal name 1A13 Deviation counter clear CLEAR 1A14 Common CLEAR COM 1A15 CW A phase PULSE PULSE F+ CCW B phase SIGN PULSE F+ 1A16 1A17 1A18
5.3 Wiring of the differential driver common terminal When the differential driver output type (QD75D1/QD75D2/QD75D4) is used, an inter-common potential difference may occur between the differential driver common terminal and the differential receiver common terminal of the drive unit. To eliminate an inter-common potential difference, connect between the differential driver common terminal of the QD75D1/QD75D2/QD75D4 and the differential receiver common terminal of the drive unit.
6. External Dimensions (1) QD75P1/QD75P2/QD75P4 QD75P1 QD75P2 QD75P1 RUN QD75P2 AX1 RUN ERR. QD75P4 QD75P4 AX1 AX2 ERR. RUN ERR. AX1 AX2 AX1 AX3 AX4 AX1 AX2 AX3 AX4 AX1 AX2 98 (3.86) 27.4 (1.08) 46 (1.81) 90 (3.54) 136 (5.
(2) QD75D1/QD75D2/QD75D4 QD75D1 QD75D1 RUN QD75D2 QD75D2 AX1 ERR. RUN QD75D4 QD75D4 AX1 AX2 ERR. RUN ERR. AX1 AX2 AX1 AX3 AX4 AX1 AX2 AX3 AX4 AX1 AX2 46 (1.81) 90 (3.54) 136 (5.35) 12 (0.47) 98 (3.86) 27.4 (1.
Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.