Specifications
GENERAL SPECIFICATIONS
Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
Operating altitude
Installation location
Overvoltage category
Pollution level
Specifications
0 to 55ºC (Note 1)
-25 to 75ºC (Note 1) (Note 2)
IEC (EN) 61131-2 Level RH-2 (5 to 95%RH: non-condensing) (Note 3)
IEC (EN) 61131-2 Level RH-2 (5 to 95%RH: non-condensing) (Note 3)
Conforming to IEC 61131-2
Conforming to IEC (EN) 61131-2 147 m/s
2
, 3 times in each of 3 directions X, Y, Z
No corrosive gases
IEC (EN) 61131-2 2000m max. (Note 4)
Inside control box
IEC (EN) 61131-2 (Category2or less) (Note 5)
IEC (EN) 61131-2 Pollution level 2 or less. (Note 6)
Under intermittent vibration Sweep count
Frequency Acceleration Amplitude
10 to 57Hz — 0.075mm
57 to 150Hz 9.8m/s
2
—
Under continuous vibration
Frequency Acceleration Amplitude
10 to 57Hz — 0.035mm
57 to 150Hz 4.9m/s
2
—
Note 1) The operating/storage ambient temperature satisfies the requirements beyond the requirements in IEC (EN) 61131-2.
Note 2) When used with the AnS series modules, the Q series PLC should be stored at -20 to 75°C.
Note 3) When used with the AnS series modules, the Q series PLC should be operated within 10 to 90%RH.
Note 4) The PLC cannot be used under pressure higher than the atmospheric pressure of altitude 0m. Doing so can cause a failure.
Note 5) This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery
within premises. Category2applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is
2500V.
Note 6) This index indicates the degree to which conductive material is generated in the environment where the equipment is used. In pollution level 2, only non-conductive pollution
occurs but temporary conductivity may be produced due to condensing.
Sweep count
10 times each in X, Y, Z
directions (for 80 min.)
General specifications indicate the environmental specifications in which this product can be installed and operated. Unless otherwise specified, the general specifications apply to all
products of the Q series. Install and operate the Q series products in the environment indicated in the general specifications.