Specifications

Connected with thermocouples/platinum temperature measuring
resistors, the Q series temperature input module can import
temperature data.
Using GX Configurator-TI (temperature input module setting/monitoring
tool), you can make initial settings and automatic refresh settings on the
screen, reducing programs.
1. The Q64TDV-GH and Q64TD are channel-isolated.
The Q64TDV-GH is a module that supports thermocouple
temperature data input and micro voltage input.
2. Detected temperature measurement values can be converted into
scaling values (%).
3.
Temperature sensors conforming to the JIS Standards are usable.
4. Includes wire break detection for temperature sensor/conductor per
channel.
The Q series temperature control modules offer a choice of optimum
temperature adjustment control.
Using GX Configurator-TC (temperature control module
setting/monitoring tool), you can make initial settings and automatic
refresh settings on the screen therefore reducing the program.
1. Direct connection of a thermocouple/platinum temperature-
measuring resistor achieves the optimum temperature adjustment
control (PID control).
2. Max. four loops temperature adjustment control can be exercised
simultaneously.
3. The Q64TCTTBW and Q64TCRTBW can detect the wire
disconnection of the heater.
Control output
Number of temperature
inputs
Accuracy
Sampling period
Number of I/O
points occupied
Q64TCTT Q64TCRT
Q64TCTTBW
16 points, 1 slot
(I/O assignment: 16 intelligent points)
32 points, 2 slots
(Default I/O assignment:
16 free points + 16 intelligent points)
Q64TCRTBW
Type
Usable thermocouple
Usable platinum temperature
measuring resistor
Voltage input range
Number of channels
Output
Wire break detection
Resolution
Accuracy
Conversion speed (Note 2)
Sampling period
Isolation system
Q64TD Q64RD
Type
16-bit signed binary
Yes (channels independent)
Temperature
conversion
value
Scaling value
Ambient
temperature
4 + cold junction compensation
-
2700 to18200
(First decimal place 10 times)
Conversion accuracy + temperature characteristic
Operating ambient temperature variation value
+ cold junction guaranteed accuracy (Note 1)
40ms/channel
Across thermocouple input and PLC base:
Transformer isolated
Across channels: Transformer isolated
Across cold junction compensation input and PLC base:
Non-isolated
A 100Mbps-compatible Ethernet interface module is available for the
first time in the industry. You can make selection according to the
system and the device on the other end.
(QJ71E71-100 only)
1. The module is compatible with 100BASE-TX to increase the
transmission speed.
2.
HTTP communication enables communication to be made using a
commercially available Web browser on a personal computer.
You can download the communication library and sample screens
that will operate on the personal computer (Web).
3. Multiple GX Developers can be connected to improve debugging
efficiency.
4. Using FTP, you can make file access to a multiple PLC system.
The Q series pulse input module realizes precision counting by setting
the optimum input filter according to the rise/fall time of the input pulses
that are to be counted. Using GX Configurator-CT (counter
setting/monitoring tool), you can make initial settings and automatic
refresh settings on the screen, reducing sequence programs.
1. Channel-isolated. (Dielectric withstand voltage: 1780VAC for 1
minute)
2. A system can be configured at low cost since a single module
includes eight pulse inputs channels.
3. An input pulse count is multiplied by user defined factor to convert
the pulse count. (Pre-scale function)
Number of channels
Input system
Input type
Input filter setting
Minimum count pulse width
(Duty ratio 50%)
Counting range
Counter type
QD60P8-G
8
5VDC/12 to 24VDC
1 phase
Frequency counter (number of sampling pulses): 16-bit binary (0 to 32767)
Totalizing counter: 0 to 99999999
Linear counter system, ring counter system
Type
QJ71E71-100
100Mbps
100BASE-TX
10BASE-T
QJ71E71
10BASE-5
10BASE-T
16
Fixed: 1kW Random: 6kW E-mail: 6kW
Yes (high-performance model QCPU only)
Remote password registration for prevention of illegal access
Compatible with A1SJ71E71/A1SJ71QE71 communication protocol
QJ71E71-B2
10Mbps
10BASE-2
Type
Communication speed
Transmission path
Number of logical ports
Send/receive buffer
Event interrupt
Remote password function
Compatibility
The B/NET is a network designed to perform centralized management
or control of power distribution equipment dispersed in a building, plant
or the like. This module enables connection of the Q series to the
B/NET.
Type
Number of stations
connected
Transmission distance
Used cable
Compatible address range
B-QIF
63 stations per module
Max. wiring length = 1km, overall wiring length = 2km
CPEV-S *1.2 (twisted pair cable) or equivalent
1 to 255 addresses
30k
33.4µs
10k
100µs
1k
1ms
100
10ms
50
20ms
10
100ms
1
1s
0.1
10s
A personal computer CPU module can be loaded on a Q series PLC base (2 slots occupied) to achieve the PC/AT compatible functions.
1. The module can achieve the personal computer functions on a PLC base, downsizing a device/control box.
2. Environmental resistance and noise resistance are on Factory Automation levels. The use of an ATA flash card and silicon disk drive
has resolved the problems of HDD life and vibration resistance. You can replace your FA personal computer or personal computer
worry-free.
3. Sequence control can be exercised by the PLC CPU and information processing performed by the personal computer CPU to achieve
integration of control and information processing, configuring an optimum system.
4. The introduction of MX Component, Soft GOT, Windows
®
compatible commercially available software and user application software
configures a highly free system.
5. The built-in Ethernet communication port helps you configure a system that utilizes the Internet/intranet technology such as E-mail and
Web access.
6. A PC card available on the market can be used for flexible system expansion.
7. The built-in USB port allows you to connect a commercially available USB device easily.
8. Using the bus interface driver software enables access to almost all I/O and intelligent function modules from a C-written application
program.(However, some modules have restrictions.)
9. The personal computer CPU module only operates in a multiple PLC configuration with PLC CPU and motion CPU, but also as a
stand alone personal computer.
10. Because of its fan-free structure, the module has improved in maintenance performance, eliminating such problems as whirled dust
particles. You can use the module worry-free in a clean room.
Partner Products
Features
Features
Features
Features
Transistor output
4 channels/module
Ambient temperature 25˚C 5˚C, input range width X ( 0.3%)
Ambient temperature 0˚C to 55˚C, input range width X ( 0.7%)
0.5s (constant regardless of the number of channels used)
Note 1: Refer to the Q64TD manual for details.
Note 2: Time from when the temperature/micro voltage is input until the conversion value
is stored into the buffer memory.
Pt100,JPt100
4-wire type and 3-wire type
4
-2000 to 8500
(First decimal place 10 times)
-200000 to 850000
(Third decimal place 1000 times)
0.025˚C
Within 0.08%
Within 0.25%
25 5˚C
0 to 55˚C
First in the industry!
Features
MPU
Memory
Video memory
IF
Silicon disk module
Hard disk module
OS
PPC-CPU686(MS)-64
64MB
PPC-CPU686(MS)-128
128MB
Type
Mobile Celeron Processor _LP 400MHz
2MB
2 channels (1 channel as extra connector)
2 channels (D-SUB 9P) (1 channel as extra connector)
1 channel (extra connector)
Mini DIN 6P
Can be used simultaneously by conversion cable.
100BASE-TX/10BASE-T
Analog RGB H-Dsub 15P
26P half connector (for connection of Contec make FDD)
PCMCIA, CardBus
Type , 2 or Type 1
Separate module (PCC-SDD(MS)-32/64/128/192/320/500/1000)
1 slot occupied
Separate module (PCC-HDD(MS)-5) 5GB
1 slot occupied
Windows
®
NT4.0, Windows
®
2000, Windows
®
NT4.0Embedded
USB
Serial
Parallel
PS2 mouse/keyboard
LAN
Display
FDD
PC card
B,R,S,N: 0.3
K,E,J,T: 0.1
Q64TDV-GH
B,R,S,E,K,J,T,N
-100mV to +100mV
B:0.7 ,R,S:0.8 ,K,T:0.3 ,E:0.2 ,
J: 0.1 , N: 0.4 , micro voltage input: 4µV
Sampling cycle 3
20ms/channel
Temperature Input Modules Channel-Isolated Pulse Input Module
Ethernet Interface Modules
(100BASE-TX Compatible)
B/NET Interface Module
Temperature Control Modules
Personal Computer CPU Modules
14 15
INCREASED NEW POSSIBILITIES OF
FACTORY AUTOMATION
3
INCREASED NEW POSSIBILITIES OF
FACTORY AUTOMATION
2