User`s manual
5 - 20 5 - 20
MELSEC-Q
5 SETUP AND PROCEDURES BEFORE OPERATION
(4) Confirming the operation status
(a) Method using GX Developer
Read the following axis monitor data with the monitor function (Buffer
memory batch).
Buffer memory address
Axis monitor data Monitor details
Axis 1Axis 2Axis 3Axis 4Axis 5Axis 6Axis 7Axis 8
Md. 1
Current feed value Monitor the current position.
70
71
170
171
270
271
370
371
470
471
570
571
670
671
770
771
Md. 3
Current speed Monitor the current speed.
74
75
174
175
274
275
374
375
474
475
574
575
674
675
774
775
Md. 4
Axis operation status
Monitor the operation status "2: JOG Operation"
of the axis.
76 176 276 376 476 576 676 776
Md. 5
Axis error code Monitor the error occurrence definition. 77 177 277 377 477 577 677 777
For more information on the monitor details, refer to "Section 4.6 List of monitor data".
(Example) Operation status of Axis 1
<GX Developer display screen>
(b) Method using GX Configurator-PT
Monitor the "current feed value", "current speed", "axis operation status"
and "axis error code" on the "Monitor/Test screen".
(For details, refer to "Section 6.6 Monitor/test".)
(Example) Operation monitor of Axis 1 (Axis #1 Monitor/Test)
<GX Configurator-PT display screen>