User`s manual

13 - 4 13 - 4
MELSEC-Q
13 TROUBLESHOOTING
Related buffer memory address
Axis 1 Axis 2 Axis 3 Axis 4 Axis 5 Axis 6 Axis 7 Axis 8
Setting range Remedy
————————
————————
Check that there is no influence from
noise.
Check hardware for possibility of fault.
————————
After switching power from OFF to
ON/resetting the PLC CPU, turn ON the
PLC READY signal (Y0) again, make
sure that the module READY signal (X0)
is ON, and then make a start. (The
module is faulty if the module READY
signal (X0) does not turn ON.)
————————
Check whether the axis stop signal (Y10
to Y17) is ON or OFF and turn OFF the
axis stop signal that is ON.
Pr. 1
Software stroke limit upper limit value
0
1
100
101
200
201
300
301
400
401
500
501
600
601
700
701
Pr. 2
Software stroke limit lower limit value
2
3
102
103
202
203
302
303
402
403
502
503
602
603
702
703
Da. 6
Positioning address/movement amount
(Refer to Section 4.5)
-2147483648 to 2147483647 (pulse)
At start: Perform JOG operation (Refer to
Chapter 10) to change "
Md. 1
Current feed value" to within the
software stroke limit range.
Current value changing:
Change the new current value to
within the software stroke limit
range (Refer to Section 9.2.4).
During operation:
Correct "
Da. 6
Positioning
address/movement amount"
(Refer to Section 4.5).
————————
————————
Review the sequence program that turns
ON/OFF the PLC READY signal (Y0).
————————
Perform JOG operation (Refer to
Chapter 10) to move the axis to the
position where the near-point dog turns
OFF, and then start machine OPR
control (Refer to Section 8.2.3, Section
8.2.7 and Section 8.2.8).
————————
After turning OFF the zero signal, start
machine OPR control (Refer to Section
8.2.5 and Section 8.2.6).
5 152 252 352 452 552 652 752
Cd. 3
Start method
0 : Positioning control
9000 : Machine OPR control
9001 : Fast OPR control
Before starting fast OPR control, perform
machine OPR control (Refer to Section
8.2).