User`s manual

9 - 12 9 - 12
MELSEC-Q
9 POSITIONING CONTROL
[2] 1-axis linear control (INC)
Operation chart
In incremental system 1-axis linear control, addresses established by a machine
OPR control are used. Position control is carried out from the current stop position
(start point address) to a position at the end of the movement amount set in "
Da. 6
Positioning address/movement amount". The movement direction is determined by
the sign of the movement amount.
Reverese direction
Forward directio
n
Start point address
(current stop position)
Movement direction for
a negative movement amount
Movement direction for
a positive movement amount
-3000 -2000 5000
Positioning control in the reverse direction (movement amount -7000)
Address after positioning control
Start point address
(current stop position)
-1000 0 1000 2000 3000 4000 6000
Example
When the start point address is 5000, and the movement amount is -7000, position control is carried
out to the -2000 position.
Positioning data setting example
The following table shows setting examples when "1-axis linear control (INC)" is set
in positioning data No. 1 of axis 1.
Setting item Setting example Setting details
Da. 1
Operation pattern
Positioning
termination
Set "Positioning termination" assuming the next positioning data will not
be executed.
Da. 2
Control method
1-axis linear
control (INC)
Set incremental system 1-axis linear control.
Da. 3
ACC/DEC time 1000ms Set the acceleration/deceleration time for position control.
Da. 4 DEC/STOP time 1000ms Set the deceleration stop time for position control.
Da. 5 Command speed 50000pulse/s Set the speed during movement.
Da. 6
Positioning address/
movement amount
-7000pulse Set the movement amount.
Axis 1 positioning data No. 1
Da. 7
Dwell time 500ms
Set the time the machine dwells after the position control stop (pulse
output stop) to the output of the positioning complete signal.
Refer to "Section 4.5 List of positioning data" for the setting details.