User`s manual

6 - 12 6 - 12
MELSEC-Q
6 UTILITY PACKAGE (GX Configurator-PT)
<Initial setting of positioning data>
Select items
to be moved
to sub window.
Move to
sub window
Axis #1
Positioning
Setting
[Explanation of items]
(1) Setting item list
Setting item
Axis #1 Parameter Setting
Axis #1 OPR data Setting
to
Axis # n Parameter Setting
Axis # n OPR data Setting
Axis #1 Positioning Data Setting
to
Axis #n Positioning Data Setting
n indicates the axis No.
QD70P4: 1 to 4 QD70P8: 1 to 8
(2) Explanation of the command buttons
Make text file
Outputs the screen display in a text file format.
End setup
Confirms the entry of set data and ends the operation.
Cancel
Cancels the set data and ends the operation.
POINT
Initial settings are stored in the intelligent module parameters.
After being written to the CPU module, the initial setting is made effective by either
(1) or (2).
(1) Cycle the RUN/STOP switch of the CPU module: STOP
RUN STOP
RUN.
(2) With the RUN/STOP switch set to RUN, turn off and then on the power or reset
the CPU module.
If the initialization settings have been written by a sequence program, the
initialization settings will be executed during the STOP
RUN of the CPU module.
Arrange so that the initial settings written by the sequence program are re-executed
during the STOP
RUN of the CPU module.