Service manual

34
Part name Check method and criterion
Measure the resistance using a tester.
(Part temperature : -10°C ~ 40°C)
Defrost thermistor/
Outdoor heat exchanger
temperature thermistor
Normal abnormal
5k ~ 55k
Open or short-circuit
Normal abnormal
100k ~ 250k
Opened or short-circuit
Normal abnormal
2.6k ~ 3.3k
Open or short-circuit
Normal
abnormal
0.40 ~ 0.49
Open or short-circuit
Measure the resistance using a tester, after warming up the thermistor by holding by hand.
(Part temperature : 20°C ~ 40°C)
Discharge temperature
thermistor
Measure the resistance between terminals using a tester.
(Winding temperature : -10°C ~ 40°C)
Compressor
W
U
V
WHT
RED
BLK
Measure the resistance between lead wires using a tester.
(Part temperature : -10°C ~ 40°C)
Outdoor fan motor
Measure the resistance using a tester. (Part temperature : -10°C ~ 40°C)
R. V. coil
Measure the resistance using a tester.(Part temperature : -10°C ~ 40°C)
Linear expansion valve
LEV
WHT
RED
YLW
BRN
ORN
BLU
Color of lead wire
Normal
WHT - RED
RED - ORN
YLW - BRN
BRN - BLU
Abnormal
Open or
short-circuit
37.4 ~ 53.9
MUZ-A18YV -
MUZ-A24YV -
MUZ-A26YV -
E1
E1
E1
MUZ-A18/A24YV
1.29 ~ 1.49
MUZ-A26YV
U
RED
WHT
BLK
V
W
(W)
(V)
(U)
Normal
RED - BLK
BLK - WHT
WHT - RED
Open or
short-circuit
(Not including
WHT - ORN)
13.4 ~ 16.4
abnormal
Pressure Normal abnormal
Operation OFF
HPS1
3.7 ± 0.15MPa
4.8 MPa
Open
Short
Other than
those list-
ed at left
0.05
0.1
+
-
High pressure switch
(HPS)
MUZ-A26YV
MUZ-A26YV
Color of
lead wire
Normal abnormal
25k ~ 100k
Open or short-circuit
Measure the resistance using a tester.
(Part temperature : 10°C ~ 40°C)
Fin temperature thermistor
2. Trouble criterion of main parts
OB346A --2qxp 04.6.14 1:20 PM Page 34