Installation manual
Wireless System Installation Guide
69-2426—01 10
Outdoor sensor (optional)
5
Mount remote controller & outdoor sensor
1 Separate the wallplate from the remote controller.
2 Mount the wallplate using the included screws and anchors 5 feet from the floor on
an interior wall. If the remote controller is configured to sense indoor temperature,
mount in the same room as the indoor unit.
Drill3/16"holesfordrywall.
Drill7/32"holesforplaster.
3 Snap the remote controller to the wallplate on the wall.
M28491
M28492
Mountthesensoronaverticalexteriorwall,atleast6inchesbelowany
overhang. Choose a location protected from direct sunlight.
Placesensorsecurely
in bracket, facing
away from wall.
RedLINK™ error codes
E0 27 Verify device temperature is within operating range. If within range for at least 30
minutes and problem persists, replace Remote Controller.
E0 91 Communication was established between wireless receiver and the indoor unit,
but communication has been lost for 10 minutes. Check cable connection. Try
replacing the cable.
E1 29 Attempting to connect incompatible wireless devices.
E1 34 Low signal strength. Move wireless device to a different location and try again.
E1 38 Make sure Connect light on wireless receiver is flashing and you are 2+ feet away
from wireless receiver.
E1 54 Indoor unit does not support wireless receiver.
Forfulllistoferrorcodes,pleaserefertoyourequipment'stechnicalservicemanual.