Specifications

53
(4) Recommended circuit
(A) Level signal
CN5
X1
X1
9
8
7
6
5
1
EB-50
Red
Orange
Max.
10 m (32 ft)
ON/OFF or
Emergency stop
External power
supply
*1
(12 or 24 VDC)
Use relays X1, X2, Y1, and Y2 that meet the following
specifications.
Contact rating
Rated voltage: 12 VDC or above
Rated current: 0.1 A or above
Minimum applied load: DC 1 mA
*1 Select an external power supply suitable for the relays
used. (12 or 24 VDC)
Connect the external power supply in the correct polarity
to input and output the signals.
Connect
5
8
(see the figure at left) to the negative
side.
Important
Be sure to use an external power supply (12 or 24
VDC) to avoid malfunctions.
Connect the external power supply in the correct
polarity to avoid malfunctions.
(B) Pulse signal
CN5
X1
X2
Y1
Y2
X1 X2 Y1 Y2
9
8
7
6
5
1
EB-50
Red
Gray
Blue
Yellow
Orange
Max.
10 m (32 ft)
External power supply
*1
(12 or 24 VDC)
ON
OFF
Prohibit
Permit
Note
The relays, external power supply, and extension cables are field supplied.
The total length of the lead wire and extension cable should not exceed 10 m (32 ft). (Use an extension cable of 0.3
mm
2
or thicker.)
Cut the excess cable near the connector, and insulate the end of unused cable with tape.