Specifications

25
(1) Maximum total length of M-NET transmission cables
a + b + d + e (f) ≤ 500 m (1640 ft)
a + b + c + g ≤ 500 m (1640 ft)
e (f) + d + c + g ≤ 500 m (1640 ft)
(2) Maximum total length of power feed for the indoor-outdoor transmission cables
g ≤ 200 m (656 ft)
d + e (f) ≤ 200 m (656 ft)
(3) Maximum total length of power feed for the centralized control transmission cables
a + b ≤ 200 m (656 ft)
a + b + c ≤ 200 m (656 ft)
Note
The M-NET remote controller cable length should be 10 m (32 ft) or shorter. The length that exceeds 10 m (32 ft) needs
to be included in the maximum total length of M-NET transmission cables (500 m (1640 ft)) and in the maximum total
length of power feed (200 m (656 ft)).
If the M-NET remote controller cable is shorter than 10 m (32 ft), the length does not need to be included in the maximum
total length.