Specifications
17
Address setting method M-NET address
Sub system controller
Assign an address that equals the group number of the smallest
controlled group plus 200.
201–250
Advanced HVAC
CONTROLLER
Assign an address that equals the address of the main indoor unit
with the lowest address in the group plus 200.
If the address overlaps with the Sub system controller's address,
assign an arbitrary but unused address between 201 and 250 to the
Advanced HVAC CONTROLLER.
201–250
DIDO controller
(PAC-YG66DCA)
Assign an arbitrary but unused address to the controller after
completing the address setting for the units with an address between
1 and 50. The number of controllable units varies with the number of
channels used.
1–50
PI controller
(PAC-YG60MCA)
Assign an arbitrary but unused address to the controller after
completing the address setting for the units with an address between
1 and 50.
1–50
AI controller
(PAC-YG63MCA)
Assign an arbitrary but unused address to the controller after
completing the address setting for the units with an address between
1 and 50.
1–50
* Some models of the units listed in the table above cannot be controlled from EB-50.