Technical Manual
82
Service
<Request Cord list>
* The Request code 150 – 152 data is the information for the indoor unit to which the remote controller is connected.
Request
code
Request content Description (Display range) Unit Remarks
0 Operation state Refer to "Operation mode" –
1 Compressor - Operating current (rms) 0 – 50 A
2 Compressor - Accumulated operating time 0 – 9999
10 hours
3 Compressor - Number of operation times 0 – 9999
100 times
4 Discharge temperature (TH4) 3 – 217 ˚C
5 Outdoor unit - Liquid pipe 1 temperature (TH3) -40 – 90 ˚C
7 Outdoor unit - 2 phase pipe temperature (TH6) -39 – 88 ˚C
9 Outdoor unit - Outside air temperature (TH7) -39 – 88 ˚C
10 Outdoor unit - Heatsink temperature (TH8) -40 – 200 ˚C
12 Discharge superheat (SHd) 0 – 255 ˚C
13 Sub - cool (SC) 0 – 130 ˚C
16 Compressor - Operating frequency 0 – 255 Hz
18 Outdoor unit - Fan output step 0 – 10 Step
22 LEV (A) opening 0 – 500 Pulses
30 Indoor unit - Setting temperature 17 – 30 ˚C
31
Indoor unit - Intake air temperature
<Measured by thermostat>
8 – 39
˚C
37 Indoor unit - Liquid pipe temperature (Unit No.1) -39 – 88 ˚C
"0" is displayed if
the target unit is
not present
38 Indoor unit - Liquid pipe temperature (Unit No.2) -39 – 88 ˚C
39 Indoor unit - Liquid pipe temperature (Unit No.3) -39 – 88 ˚C
40 Indoor unit - Liquid pipe temperature (Unit No.4) -39 – 88 ˚C
42 Indoor unit - Cond./ Eva. pipe temperature (Unit No.1) -39 – 88 ˚C
43 Indoor unit - Cond./ Eva. pipe temperature (Unit No.2) -39 – 88 ˚C
44 Indoor unit - Cond./ Eva. pipe temperature (Unit No.3) -39 – 88 ˚C
45 Indoor unit - Cond./ Eva. pipe temperature (Unit No.4) -39 – 88 ˚C
100
Outdoor unit - Error postponement history 1 (latest) Displays postponement code
("--" is displayed if no postpone-
ment code is present)
Code
103 Error history 1 (latest) Displays error history
("--" is displayed if no history is
present)
Code
104 Error history 2 (Second to last) Displays error history
("--" is displayed if no history is
present)
Code
107 Operation mode at time of error Displayed in the same way as
request code "0"
–
150 Indoor - Actual intake air temperature -39 – 88 ˚C
151 Indoor - Liquid pipe temperature -39 – 88 ˚C
152 Indoor - 2 phase pipe temperature -39 – 88 ˚C